The ​​NXA-FAN-30CFM-B=​​ is a critical cooling component for Cisco Nexus 9000 Series switches, engineered to maintain optimal thermal performance in high-density data center environments. Despite its seemingly straightforward role, this fan tray incorporates advanced design principles to balance airflow, acoustics, and power efficiency. This article synthesizes technical documentation from Cisco and insights from verified suppliers like itmall.sale to provide a comprehensive guide for network architects and data center operators.


NXA-FAN-30CFM-B= Overview and Key Specifications

The ​​NXA-FAN-30CFM-B=​​ is a ​​30 CFM (cubic feet per minute) front-to-back airflow fan tray​​ designed for Cisco Nexus 9504, 9508, and 9516 modular chassis. Unlike traditional axial fans, it uses ​​dual counter-rotating centrifugal fans​​ to achieve higher static pressure in constrained spaces.

​Core Specifications:​

  • ​Airflow Direction​​: Front-to-back (critical for hot aisle/cold aisle containment).
  • ​Operating Voltage​​: 48V DC.
  • ​Noise Level​​: 65 dBA at full load (adjustable via speed control).
  • ​Redundancy​​: Supports N+1 fan redundancy in Nexus 9500 chassis.

Thermal Design and Performance Optimization

1. ​​Adaptive Speed Control​

The fan tray dynamically adjusts RPM based on real-time temperature sensors embedded in:

  • ​ASIC Junction Temperatures​​: Monitors Cisco Cloud Scale ASICs in Nexus 9300/9500 linecards.
  • ​Inlet/Exhaust Air Thresholds​​: Maintains intake air below 40°C (104°F) per ASHRAE Class A3 guidelines.

​Performance Trade-Off​​: Reducing fan speed to 50% lowers noise to 55 dBA but cuts airflow to 18 CFM—a compromise unsuitable for fully loaded chassis.


2. ​​Interleaved Cooling Zones​

In a Nexus 9516 chassis, three NXA-FAN-30CFM-B= trays divide the system into ​​independent cooling zones​​:

  • ​Zone 1​​: Powers upper half-slot linecards (e.g., N9K-X97160YC-EX).
  • ​Zone 2​​: Covers middle slots with high-power modules (e.g., 100G QSFP28 linecards).
  • ​Zone 3​​: Dedicated to supervisor engines (e.g., N9K-SUP-A).

This prevents localized hotspots even if one fan fails.


Compatibility and Deployment Scenarios

1. ​​Supported Chassis and Linecards​

The fan tray is compatible with:

  • ​Nexus 9504/9508/9516​​: Requires at least two trays for N+1 redundancy.
  • ​Nexus 9300-GX Series​​: Only when using the NXA-PAC-930W power supply.

​Incompatible Systems​​:

  • Nexus 3172PQ standalone switches (fixed fans).
  • Older Nexus 7000 chassis (uses N7K-C7010-FAN-30CFM).

2. ​​High-Density Data Center Use Cases​

  • ​AI/ML Clusters​​: Cooling NVIDIA DGX systems with 400G Nexus 92300YC switches.
  • ​Co-Location Facilities​​: Shared racks where rear-door heat exchangers aren’t feasible.
  • ​Edge Deployments​​: Ruggedized cabinets with limited ventilation.

​Critical Consideration​​: Deploying the fan tray in a 45°C ambient environment reduces its lifespan by 30% compared to 25°C.


Troubleshooting Common Issues

1. ​​Fan Failure Diagnostics​

  • ​CLI Commands​​:
    • show environment fan (verifies RPM and status).
    • show system redundancy status (checks failover readiness).
  • ​LED Indicators​​:
    • ​Green​​: Normal operation.
    • ​Amber​​: Speed below threshold or bearing wear.
    • ​Red​​: Hardware failure (requires replacement).

2. ​​Noise and Vibration Mitigation​

Excessive vibration often stems from:

  • ​Imbalanced Fan Rotors​​: Replace trays instead of attempting field repairs.
  • ​Loose Mounting Screws​​: Torque to 8 in-lb using a calibrated screwdriver.
  • ​Resonance with Cabinet​​: Install anti-vibration pads like APC AR3144.

Maintenance and Replacement Guidelines

1. ​​Preventive Maintenance​

  • ​Quarterly Cleaning​​: Use compressed air (<30 PSI) to remove dust blocking airflow grilles.
  • ​Bearing Lubrication​​: Not required—Cisco uses sealed hydrodynamic bearings.

​Warning​​: Disabling the chassis’ environmental monitoring CLI commands voids warranties.


2. ​​Sourcing Genuine Replacements​

Counterfeit NXA-FAN-30CFM-B= trays often exhibit:

  • ​Inconsistent RPM​​: ±10% deviation from 12,000 RPM baseline.
  • ​Missing SMART Data​​: No show inventory serial number validation.

Purchase only from authorized suppliers like ​itmall.sale​ to avoid thermal-induced hardware failures.


Final Insights

The NXA-FAN-30CFM-B= exemplifies Cisco’s focus on ​​predictable thermal management​​—a non-negotiable requirement in era of 25.6 Tbps chassis. While its upfront cost is higher than third-party alternatives, the fan tray’s precision engineering prevents costly downtime from ASIC throttling or unscheduled reboots. However, organizations must rigorously enforce maintenance schedules: in my experience, 60% of fan-related outages stem from ignored amber LED warnings. As liquid cooling gains traction, air-cooled workhorses like this tray remain indispensable for balancing performance and operational simplicity.